Model GDS-MV

Gas Density Switch

Selected documents
Sales contact Questions? Find a contact in your vicinity.

Applications

  • Gas density monitoring of closed SF6 tanks
  • For medium voltage switchgear
  • For the use in ring main units

Special Features

  • Density switch with reference chamber and gas compensation. Without influence of altitude and atmospheric pressure change; no recalibration necessary

Description

Working ranges
Permissible filling pressure (tank pressure) at +20 °C: 5 bar abs.

Permissible temperature ranges
Ambient: -20 … +60 °C (gas phase)
Storage: -40 … +80 °C

Alarm contacts / Contact rating
1 or 2 micro switches to make or break, switching points according to customer’s requirement and secured
Contact rating: 5 A / 250 V AC, 50 Hz

Switching distance
Between 2 contacts:  ≥ 50 mbar
Switching hysteresis: typically 50 mbar

Switching accuracy of reference contact
at 20° C:              ≤ ±40 mbar
at -20 … +60 °C: ≤ ±60 mbar

High-voltage test
2 kV, 50 Hz, 1s (wiring versus case)

Electrical connection
Standard: open-ended cable, length 0.3 m

Process connection
Stainless steel, bottom, G 1/4 B (male), 14 mm flats

Pressure element
Capsule spring, stainless steel, welded
Gas tight:      leakage rate ≤ 1 · 10-8 mbar · l / s
Test method: spectrometry of helium mass

Gas Density Switch
  • Gas Density Switch
Wish list - Documents (0)

There are currently no documents on your wish list. You can add any document from the download area to your wish list. To do this, select the desired language using the flag symbol.

The maximum number of 20 entries was reached.

To receive your download link via e-mail, enter your address here: