Model GDS-HV

Gas Density Switch

Selected documents
Sales contact Questions? Find a contact in your vicinity.

Applications

  • Gas density monitoring of closed SF6 tanks
  • For outdoor use
  • For high voltage switchgear

Special Features

  • Density switch with reference chamber and gas compensation.
  • Micro switch inside the reference chamber; without influence of atmospheric pressure change and altitude; no recalibration necessary

Description

Working ranges
Permissible filling pressure:
11.0 barabs. / 20 °C
Maximum pressure of reference chamber:
7.5 barabs. / 20 °C
Minimum pressure of reference chamber:
4.0 barabs. / 20 °C

Permissible temperature ranges
Ambient: -40 … +80 °C (gas phase)
Storage: -40 … +80 °C

Alarm contacts / Contact rating
Up to four micro switches, to make or break as ordered, switching points non adjustable and secured
Contact rating: 5 A / 250 V AC, 50 Hz

Switching distance
Maximum switching point distance: 1.6 bar
Minimum switching point distance: 0.1 bar
Switching hysteresis: typical 0.1 bar , Switching point setting as per specification

Switching accuracy of reference contact
at 20 °C:             60 mbar
at -20 ... +60 °C: 80 mbar

High-voltage test
2 kV, 50 Hz, 1s (wiring versus case)

Electrical connection
Cable box with cable gland M20 x 1.5
Connection cross-section max. 2.5 mm²

Gas Density Switch
  • Gas Density Switch
Wish list - Documents (0)

There are currently no documents on your wish list. You can add any document from the download area to your wish list. To do this, select the desired language using the flag symbol.

The maximum number of 20 entries was reached.

To receive your download link via e-mail, enter your address here: